1
/
of
1
woer
integral prefabricated intermediate joint
integral prefabricated intermediate joint
Regular price
0₫
Regular price
Sale price
0₫
Unit price
/
per
Couldn't load pickup availability
Application areas:
Primarily used in high-voltage AC power transmission, for connections between high-voltage power cables.
Product Description
- The joint has a compact structure, is easy to install, has a long creepage distance in the rubber insulation, and has a large design flexibility, making it suitable for long-term stable operation in particularly humid areas.
- The outer sheath adopts a high-strength protective shell and a waterproof and insulating sealing structure, which has good mechanical and sealing performance, as well as good corrosion resistance, ensuring the safe operation of the joint in harsh environments for a long time.
- It has good explosion-proof performance and will not form fragments that could endanger personal or equipment safety in the event of an accident;
- The outermost layer can be fitted with a fiberglass outer protective box, and the inside is filled with high-voltage cable waterproof sealant to enhance its waterproof performance.
Product Parameters
| name | Integral prefabricated intermediate joint | |
|---|---|---|
| Model Specifications | WYJJTI、WYJJJI | WYJJTI、WYJJJI |
| Implementation Standards | IEC60840, GB/T11017 | IEC62067, GB/Z18890 |
| Rated voltage (U0/U) | 64/110kV | 127/220kV |
| Maximum operating voltage (Um) | 126kV | 252kV |
| Baseline Impact Resistance Level (BIL) | 550kV | 1050kV |
| Maximum rated temperature of conductor | ||
| a): During normal operation | 90℃ | 90℃ |
| b): Transient (short circuit time not exceeding 5 seconds) | 250℃ | 250℃ |
| Insulating materials | Imported EPDM rubber | Imported EPDM rubber |
| Stress cone material | Imported EPDM rubber | Imported EPDM rubber |
| The connector is suitable for cables with the following outer diameter (after grinding). | Φ56-85mm | Φ80-116mm |
| Storage conditions and shelf life | Store in a cool, dry, sealed container away from light. 5 years. | Store in a cool, dry, sealed container away from light. 5 years. |
| Relative permittivity of insulation | 2.3-3.2 | 2.3-3.2 |
| Volume resistivity of insulation | ≥1×10¹⁵Ω·cm | ≥1×10¹⁵Ω·cm |
| Connecting pipe | ||
| a): Crimping process description | Hexagonal compression | Hexagonal compression |
| b): Dimensions of the crimping die | Selected according to cable conductor cross-section | Selected according to cable conductor cross-section |
| weight | 120kg | 160kg |
| Sealing method of the joint | Waterproof tape, heat shrink tubing, cable sealant | Waterproof tape, heat shrink tubing, cable sealant |
| Electrical connection method for grounding with metal sheath | Welding or sealing lead | Welding or sealing lead |
| Enhanced protective case (optional) | ||
| a): Materials | Fiberglass | Fiberglass |
| b): External dimensions | 2100×500×400 | 2850×600×600 |
| Waterproof materials | ||
| a): Materials | polyurethane | polyurethane |
| b): Quantity | 125kg | 175kg |
| Insulating joint metal sheath | ||
| a) Withstands DC voltage | 20kV | 25kV |
| b) Withstands impulse voltage | 75kV | 95kV |
Product Selection
Straight-through intermediate connector: WYJJTI type
Insulated intermediate joint: WYJJJI type
- Rated voltage: 48/66kV, applicable to 120~1600mm²
- Rated voltage: 64/110kV, applicable to 240~1600mm²
- Rated voltage: 76/138kV, applicable to 240~1600mm²
- Rated voltage: 127/220kV, applicable to 400~2500mm²
Share