woer

64/110kV Cross-linked Polyethylene Cable Shielding Repair Joint

64/110kV Cross-linked Polyethylene Cable Shielding Repair Joint

Regular price 0₫
Regular price Sale price 0₫
Sale Sold out

Application areas:

The 110kV wrapped-type straight-through dummy joint is suitable for repairing damaged cable outer shielding, restoring the cable's structure and electrical performance. The 110kV wrapped-type insulated dummy joint can not only repair cables with damaged outer shielding, but also serve as a cross-interconnection grounding in long 110kV lines.

Product Description

The 110kV cross-linked polyethylene (XLPE) cable shielding and isolating joint restores the cable's outer shielding layer through a tape wrapping process. A stress cone structure is also wrapped around the tape to disperse the electric field. Each tape possesses specialized electrical properties, and its self-adhesive and self-fusing properties allow for rapid fusion between the tape and the cable, and between different tapes, significantly reducing the possibility of gaps during construction. The 110kV XLPE cable shielding and isolating joint repairs the cable's outer shielding layer without cutting the cable core, greatly reducing the problem of excessive resistance at cable joints. The cable's insulation layer remains undamaged, preserving its excellent insulation performance.

交联聚乙烯电缆屏蔽修复接头安装示意图.gif

Product Parameters

Electrical performance of 110kV cross-linked polyethylene cable shield repair joint

Power frequency withstand voltage (AC) 160kV/40min No penetration, no flashover
Partial discharge 96kV ≤10pC
Impulse voltage 550kV (10 times each for positive and negative polarities) No penetration, no flashover
Note: This product meets the requirements of IEC 60885-3 and GB/T 3048.12.

Product Selection

  • Model: WYJZGGC
    Suitable for both indoor and outdoor use
    Applicable cable standard cross-section: 240-1600mm²
    The terminal insulation level, current carrying capacity, long-term operating temperature, and short-circuit temperature all meet the technical requirements of the cables they are used with.
View full details