woer
Dry plug-in composite sleeve terminal
Dry plug-in composite sleeve terminal
Couldn't load pickup availability
Application areas:
Dry-type pluggable composite bushing terminals for AC power transmission, including 66kV and 110kV cross-linked polyethylene insulated power cables.
Product Description
1. The external insulation of the terminal uses silicone rubber sheds, which have excellent dirt resistance, UV resistance, aging resistance and explosion-proof performance;
2. The cable handling length is only 1/6 of that of a conventional outdoor terminal, greatly shortening the installation time;
3. The terminal is plugged into the cable, making installation simple and maintenance easy;
4. The terminal has a completely dry structure, eliminating leakage problems.
Product Parameters
| Serial Number | project | parameter |
|---|---|---|
| 1 | Plug-in outdoor terminal | |
| 1.1 | Specification | WYJZWGF4 (WYJZWFG4) |
| 1.2 | Implementation Standards | IEC60840 GB/T11017 |
| 1.3 | Rated voltage (Uo/U) | 64/110kV |
| 1.4 | Maximum operating voltage (Um) | 126kV |
| 1.5 | Baseline Impact Resistance Level (BIL) | 550kV |
| 1.6 | Maximum rated temperature of conductor: | |
| a) During normal operation | 90℃ | |
| b) Transient (short-circuit current duration not exceeding 5s) | 250℃ | |
| 1.7 | Insulating components | |
| a) Materials and colors | Epoxy resin and imported silicone rubber/grey | |
| b) Climb distance | 4032mm | |
| c) Mechanical property description | Horizontal load 2kN | |
| 1.8 | Stress cone | |
| a) Materials | Imported EPDM rubber | |
| b) Storage conditions and shelf life | Cool and dry place, 5 years | |
| 1.9 | Terminal weight | 200kg |
| 1.10 | high | 1715mm |
| 1.11 | Tail end sealing form | Waterproof tape, epoxy putty, heat shrink tubing |
| 1.12 | Metal grounding of the terminal | |
| a) Connection method | Welding or sealing lead | |
| b) Equivalent cross section | ≥240mm2 | |
| d) Allowable maximum short-circuit current | Consistent with cables |
Product Selection
WYJZWGF4 (WYJZWFG4) type: Suitable for outdoor pollution level IV.
Rated voltage: 48/66kV, applicable to 120~1000mm²
Rated voltage: 64/110kV, applicable to 240~800mm²
Share