Skip to product information
1 of 1

woer

Prefabricated GIS terminal

Prefabricated GIS terminal

Regular price 0₫
Regular price Sale price 0₫
Sale Sold out

Application areas:

Primarily used in AC high-voltage power transmission, suitable for connecting cables to sulfur hexafluoride gas-insulated switchgear, and for connecting power cables to high-voltage transformers.

Product Description

  • 1. The stress cone material is made of imported EPDM rubber, which is resistant to thermal shock, leakage current, and has high breakdown strength. It also possesses excellent interfacial, thermal, and thermodynamic properties.
  • 2. The structure of spring-pressing the profit cone onto the conical wall of the epoxy sleeve overcomes the drawbacks of elastic relaxation caused by material aging of the stress cone and poor contact between the stress cone and the outer semiconductive layer of the cable, thus ensuring the long-term safe operation of the terminal.
  • 3. The entire terminal is a completely dry structure, requiring no additional insulating casting agent. Therefore, there is no accelerated aging of the stress cone due to immersion in insulating casting agent, thus improving the service life of the stress cone. Furthermore, it eliminates the possibility of oil leakage and other related phenomena during operation.
  • 4. The terminal has a fully dry structure. All electrical connections and insulation components of the terminal are placed inside a metal casing, which is fully shielded and surface-mounted.
  • 4. This terminal is suitable for indoor/outdoor use. Since the terminal does not come into contact with the atmospheric environment, environmental conditions, stain levels, and altitudes are all considered unrestricted.

Product Parameters

Serial Number project Parameters (110kV) Parameters (220kV)
1 name Prefabricated GIS terminal Prefabricated GIS terminal
1.1 Specification WYJZGG WYJZGG
1.2 Implementation Standards IEC60840 IEC62271
GB/T11017
IEC62067 IEC62271
GB/Z 18890
1.3 Rated voltage (Uo/U) 64/110kV 127/220kV
1.4 Maximum operating voltage (Um) 126kV 252kV
1.5 Baseline Impact Resistance Level (BIL) 550kV 1050kV
1.6 Maximum rated temperature of conductor:
a) During normal operation 90℃ 90℃
b) Transient (short-circuit current duration not exceeding 5 seconds) 250℃ 250℃
1.7 insulating sleeve
a) Materials Epoxy resin Epoxy resin
b) Length 631mm 1152mm
1.8 Precast stress cone
a) Materials Imported EPDM rubber Imported EPDM rubber
b) Storage conditions and shelf life Cool and dry place, 5 years Cool and dry place, 5 years
1.9 Terminal weight 60kg 210kg
1.10 high 757mm 960mm
1.12 Tailpipe sealing type Waterproof tape, heat shrink tubing Waterproof tape, heat shrink tubing
1.13 Other insulating media inside the casing dry dry
1.14 Metal grounding of the terminal
b) Specifications and quantity ≥240mm2 ≥240mm2
c) Equivalent cross section Consistent with cables Consistent with cables
d) Allowable maximum short-circuit current Consistent with cables Consistent with cables

Product Selection

  • WYJZGG type: Indoor use
  • Rated voltage: 48/66kV, applicable to 120~1600mm²
  • Rated voltage: 64/110kV, applicable to 240~1600mm²
  • Rated voltage: 76/138kV, applicable to 240~1600mm²
  • Rated voltage: 127/220kV, applicable to 400~2500mm²
View full details