1
/
of
1
woer
Prefabricated GIS terminal
Prefabricated GIS terminal
Regular price
0₫
Regular price
Sale price
0₫
Unit price
/
per
Couldn't load pickup availability
Application areas:
Primarily used in AC high-voltage power transmission, suitable for connecting cables to sulfur hexafluoride gas-insulated switchgear, and for connecting power cables to high-voltage transformers.
Product Description
- 1. The stress cone material is made of imported EPDM rubber, which is resistant to thermal shock, leakage current, and has high breakdown strength. It also possesses excellent interfacial, thermal, and thermodynamic properties.
- 2. The structure of spring-pressing the profit cone onto the conical wall of the epoxy sleeve overcomes the drawbacks of elastic relaxation caused by material aging of the stress cone and poor contact between the stress cone and the outer semiconductive layer of the cable, thus ensuring the long-term safe operation of the terminal.
- 3. The entire terminal is a completely dry structure, requiring no additional insulating casting agent. Therefore, there is no accelerated aging of the stress cone due to immersion in insulating casting agent, thus improving the service life of the stress cone. Furthermore, it eliminates the possibility of oil leakage and other related phenomena during operation.
- 4. The terminal has a fully dry structure. All electrical connections and insulation components of the terminal are placed inside a metal casing, which is fully shielded and surface-mounted.
- 4. This terminal is suitable for indoor/outdoor use. Since the terminal does not come into contact with the atmospheric environment, environmental conditions, stain levels, and altitudes are all considered unrestricted.
Product Parameters
| Serial Number | project | Parameters (110kV) | Parameters (220kV) |
|---|---|---|---|
| 1 | name | Prefabricated GIS terminal | Prefabricated GIS terminal |
| 1.1 | Specification | WYJZGG | WYJZGG |
| 1.2 | Implementation Standards | IEC60840 IEC62271 GB/T11017 |
IEC62067 IEC62271 GB/Z 18890 |
| 1.3 | Rated voltage (Uo/U) | 64/110kV | 127/220kV |
| 1.4 | Maximum operating voltage (Um) | 126kV | 252kV |
| 1.5 | Baseline Impact Resistance Level (BIL) | 550kV | 1050kV |
| 1.6 | Maximum rated temperature of conductor: | ||
| a) During normal operation | 90℃ | 90℃ | |
| b) Transient (short-circuit current duration not exceeding 5 seconds) | 250℃ | 250℃ | |
| 1.7 | insulating sleeve | ||
| a) Materials | Epoxy resin | Epoxy resin | |
| b) Length | 631mm | 1152mm | |
| 1.8 | Precast stress cone | ||
| a) Materials | Imported EPDM rubber | Imported EPDM rubber | |
| b) Storage conditions and shelf life | Cool and dry place, 5 years | Cool and dry place, 5 years | |
| 1.9 | Terminal weight | 60kg | 210kg |
| 1.10 | high | 757mm | 960mm |
| 1.12 | Tailpipe sealing type | Waterproof tape, heat shrink tubing | Waterproof tape, heat shrink tubing |
| 1.13 | Other insulating media inside the casing | dry | dry |
| 1.14 | Metal grounding of the terminal | ||
| b) Specifications and quantity | ≥240mm2 | ≥240mm2 | |
| c) Equivalent cross section | Consistent with cables | Consistent with cables | |
| d) Allowable maximum short-circuit current | Consistent with cables | Consistent with cables |
Product Selection
- WYJZGG type: Indoor use
- Rated voltage: 48/66kV, applicable to 120~1600mm²
- Rated voltage: 64/110kV, applicable to 240~1600mm²
- Rated voltage: 76/138kV, applicable to 240~1600mm²
- Rated voltage: 127/220kV, applicable to 400~2500mm²
Share